DICOM PS3.15 2021e - Security and System Management Profiles

A.5.3.13 Order Record

This message describes the event of an order being created, modified, accessed, or deleted. This message may only include information about a single patient.

Note

An order record typically is managed by a non-DICOM system. However, DICOM applications often manipulate order records, and thus may be obligated by site security policies to record such events in the audit logs.

Table A.5.3.13-1. Audit Message for Order Record

Real World Entities

Field Name

Opt.

Value Constraints

Event

EventID

M

EV (110109, DCM, "Order Record")

EventActionCode

M

Enumerated value:

C = create

R = read

U = update

D = delete

EventDateTime

M

not specialized

EventOutcomeIndicator

M

not specialized

EventTypeCode

U

not specialized

User (1..2)

UserID

M

The identity of the person or process manipulating the data. If both the person and the process are known, both shall be included.

AlternateUserID

U

not specialized

UserName

U

not specialized

UserIsRequestor

U

not specialized

RoleIDCode

U

not specialized

NetworkAccessPointTypeCode

U

not specialized

NetworkAccessPointID

U

not specialized

Patient (1)

ParticipantObjectTypeCode

M

EV 1 (person)

ParticipantObjectTypeCodeRole

M

EV 1 (patient)

ParticipantObjectDataLifeCycle

U

not specialized

ParticipantObjectIDTypeCode

M

EV 2 (patient ID)

ParticipantObjectSensitivity

U

not specialized

ParticipantObjectID

M

The patient ID

ParticipantObjectName

U

The patient name

ParticipantObjectQuery

U

not specialized

ParticipantObjectDetail

U

not specialized

ParticipantObjectDescription

U

not further specialized


DICOM PS3.15 2021e - Security and System Management Profiles