DICOM PS3.15 2017d - Security and System Management Profiles

A.5.3.3 Begin Transferring DICOM Instances

This message describes the event of a system beginning to transfer a set of DICOM instances from one node to another node within control of the system's security domain. This message may only include information about a single patient.

Note

A separate Instances Transferred message is defined for transfer completion, allowing comparison of what was intended to be sent and what was actually sent.

Table A.5.3.3-1. Audit Message for Begin Transferring DICOM Instances

Real World Entities

Field Name

Opt.

Value Constraints

Event

EventID

M

EV (110102, DCM, "Begin Transferring DICOM Instances")

EventActionCode

M

Shall be: E = Execute

EventDateTime

M

not specialized

EventOutcomeIndicator

M

not specialized

EventTypeCode

U

not specialized

Active Participant:

Process Sending the Data (1)

UserID

M

The identity of the process sending the data.

AlternativeUserID

U

not specialized

UserName

U

not specialized

UserIsRequestor

M

not specialized

RoleIDCode

M

EV (110153, DCM, "Source Role ID")

NetworkAccessPointTypeCode

U

not specialized

NetworkAccessPointID

U

not specialized

Active Participant:

Process receiving the data (1)

UserID

M

The identity of the process receiving the data.

AlternativeUserID

U

not specialized

UserName

U

not specialized

UserIsRequestor

M

not specialized

RoleIDCode

M

EV (110152, DCM, "Destination Role ID")

NetworkAccessPointTypeCode

U

not specialized

NetworkAccessPointID

U

not specialized

Active Participant:

Other Participants (0..N)

UserID

M

The identity of any other participants that might be involved and known, especially third parties that are the requestor

AlternativeUserID

U

not specialized

UserName

U

not specialized

UserIsRequestor

M

not specialized

RoleIDCode

U

not specialized

NetworkAccessPointTypeCode

U

not specialized

NetworkAccessPointID

U

not specialized

Participating Object:

Studies being transferred (1..N)

ParticipantObjectTypeCode

M

Shall be: 2 = system

ParticipantObjectTypeCodeRole

M

Shall be: 3 = report

ParticipantObjectDataLifeCycle

U

not specialized

ParticipantObjectIDTypeCode

M

EV (110180, DCM, "Study Instance UID")

ParticipantObjectSensitivity

U

not specialized

ParticipantObjectID

M

The Study Instance UID

ParticipantObjectName

U

not specialized

ParticipantObjectQuery

U

not specialized

ParticipantObjectDetail

U

Element "ContainsSOPClass" with one or more SOP Class UID values

ParticipantObjectDescription

U

not specialized

SOPClass

MC

not specialized

Accession

U

not specialized

NumberOfInstances

U

not specialized

Instances

U

not specialized

Encrypted

U

not specialized

Anonymized

U

not specialized

Participating Object:

Patient (1)

ParticipantObjectTypeCode

M

Shall be: 1 = person

ParticipantObjectTypeCodeRole

M

Shall be: 1 = patient

ParticipantObjectDataLifeCycle

U

not specialized

ParticipantObjectIDTypeCode

M

Shall be: 2 = patient ID

ParticipantObjectSensitivity

U

not specialized

ParticipantObjectID

M

The patient ID

ParticipantObjectName

U

The patient name

ParticipantObjectQuery

U

not specialized

ParticipantObjectDetail

U

not specialized

ParticipantObjectDescription

U

not specialized


DICOM PS3.15 2017d - Security and System Management Profiles